CATALOGUE PRODUCT

ARB4-A3

Arc Flash Protection Relay

Three-channel arc-sensor acquisition relay for arc protection in 0.4-35 kV distribution systems.

← All products
ARB4-A3 Arc Flash Protection RelayARB4-A3 product photograph extracted from the supplied catalogue.

PRODUCT IDENTITY

Catalogue record

Source catalogue
SST固态变压器配套产品明细.xls
Original product name
弧光保护装置
Catalogue model
ARB4-A3
Source location
Sheet1, rows 6, 13, 15
Catalogue installation location
中置柜 / 输入柜 / 功率柜
Image source
Sheet1!E6 · xl/media/image12.jpeg
Source notes
  • Only ARB4-A3 is selected; the A1/A2 channel counts are not applied to it.
  • Action-time values are device-action test results with the conditions stated in section 2.2; they are not a promise of complete fault-clearing time.
  • The manual describes an ARB4 device with ARB-S arc sensors and optical fiber. Components and quantities are separate configuration details.
013 arc-sensor acquisition channels
02Arc-only or dual-criterion protection
03Arc-sensor and fiber-link self-inspection

PRODUCT OVERVIEW

Product information

ARB4-A3 is the three-channel version in the ARB4 selection table. The manual lists arc-only, arc-and-current and arc-and-zero-sequence-voltage criteria, fault-point location, sensor/fiber-link self-inspection, fault recording and event recording. Action-time values below retain the manual's input and relay-output test conditions.

Listed model

ARB4-A3

TECHNICAL DETAILS

Specifications and their sources

System application
0.4-35 kV distribution systemsSource: ARB4 v1.2, PDF p.9, section 1.1 Information
Arc-sensor acquisition — A3
3 channelsSource: ARB4 v1.2, PDF p.16, section 1.4 Selection guide, ARB4-A3 column
Analogue inputs
4 current channels; 3 zero-sequence-voltage channelsSource: ARB4 v1.2, PDF p.16, section 1.4 Selection guide
Digital I/O
8 active inputs; 5 normally-open outputsSource: ARB4 v1.2, PDF pp.11,16, interface resources and selection guide
Auxiliary-supply options
AC/DC 220 V, AC/DC 110 V, DC 48 V or DC 24 V; rated voltage × (1 ±20%); ≤15 VASource: ARB4 v1.2, PDF p.18, section 2.1.1 Power supply
Communication / time synchronization
One RS485 interface with Modbus or IEC 60870-5-103; RS485 and IRIG-B are multiplexed, select oneSource: ARB4 v1.2, PDF pp.16-17, selection guide and its note
Arc-only action time
≤3.8 ms at twice the arc action threshold, using electromagnetic relay outputSource: ARB4 v1.2, PDF p.21, section 2.2 Basic mechanical design feature
Arc-and-current action time
≤7.8 ms at twice the arc threshold and twice the current setting, using electromagnetic relay outputSource: ARB4 v1.2, PDF p.21, section 2.2 Basic mechanical design feature

CATALOGUE IMAGES

Additional views from the catalogue

Original catalogue product photograph, cell F6.
Original catalogue product photograph, cell F6.Catalogue · Sheet1!F6
Original catalogue product photograph, cell G6.
Original catalogue product photograph, cell G6.Catalogue · Sheet1!G6
Original catalogue product photograph, cell H6.
Original catalogue product photograph, cell H6.Catalogue · Sheet1!H6

CATALOGUE APPLICATION

Listed installation context

01SST withdrawable switchgear cabinet
02SST input cabinet
03SST power cabinet

SOURCE DOCUMENTS

Original product manuals

ARB4 Arc Flash Protection Relay — Operational Manual

Chinese / English / Russian · v1.2 · Relevant PDF pages 9, 11, 16, 17, 18, 21

Download original manual ↓

PRODUCT QUESTIONS

Questions about this model

How many arc-sensor acquisition channels does ARB4-A3 provide?

The model-selection table lists three channels for A3, two for A2 and one for A1. This entry describes A3.

Is 3.8 ms the total fault-clearing time?

No. The manual states arc-only relay action time ≤3.8 ms at twice the arc action threshold with electromagnetic relay output. It is not a total system or circuit-breaker fault-clearing-time specification.

Can RS485 and IRIG-B operate together?

The manual states that these interfaces are multiplexed and only one can be selected.

PROJECT SUPPORT

Evaluating ARB4-A3?

Send the application, voltage, required functions, quantity and target delivery date.

Send project requirements →