CATALOGUE PRODUCT
ASD300-TH-WH2-P12-C-400
Switch Cabinet Integrated Measuring and Control Device
ASD300 configuration with 12 wireless temperature points, two temperature/humidity control circuits and communication, as identified by its catalog ordering code.
← All products
ASD300-TH-WH2-P12-C-400 product photograph extracted from the supplied catalogue.PRODUCT IDENTITY
Catalogue record
- Source catalogue
- SST固态变压器配套产品明细.xls
- Original product name
- 开关柜智能操控装置
- Catalogue model
- ASD300-TH-WH2-P12-C-400
- Source location
- Sheet1, row 4
- Catalogue installation location
- 中置柜
- Image source
- Sheet1!E4 · xl/media/image4.jpeg
- The exact catalog ordering code is retained. The TH, WH2, P12, C and 400 fields are decoded from Figure 1.1.
- The 100 V /5 A entries are the ASD300 metering inputs; they are not the switchgear system-voltage rating.
- Wireless temperature, electrical metering and communication must not be generalized to every ASD family member.
PRODUCT OVERVIEW
Product information
The manual's naming rule identifies T as the opening/closing, remote/local and charging switches; H as charging indication; WH2 as two temperature/humidity control circuits; P12 as 12 wireless temperature points; C as communication; and 400 as ATE400 wireless temperature sensors. The ASD300 base model also provides the metering functions shown in its model table.
Listed model
TECHNICAL DETAILS
Specifications and their sources
- Switchgear application
- 3-35 kV indoor switchgearSource: ASD V3.2, PDF p.6, section 1.1 Product overview
- T / H configuration
- Opening/closing, remote/local and charging switches; charging indicationSource: ASD V3.2, PDF p.7, Figure 1.1 Product naming rule
- Temperature/humidity control
- WH2: two temperature/humidity control circuitsSource: ASD V3.2, PDF p.7, Figure 1.1 Product naming rule
- Wireless temperature configuration
- P12: 12 points; 400: ATE400 sensorsSource: ASD V3.2, PDF p.7, Figure 1.1 Product naming rule
- Auxiliary supply
- AC 85-265 V or DC 100-300 VSource: ASD V3.2, PDF p.10, Table 2 ASD Series Technical data
- ASD300 metering inputs
- 100 V; 5 A; 50 Hz; 3P3L or 3P4LSource: ASD V3.2, PDF p.9, Table 2 ASD300 Rated input column
- Communication
- RS485; Modbus RTU; 2400 /4800 /9600 /19200 bpsSource: ASD V3.2, PDF pp.9-10, Tables 1-2 communication rows
- Wireless temperature range / accuracy
- -50 to +125 °C /±1 °CSource: ASD V3.2, PDF p.10, Table 2 ASD300 wireless temperature rows
- ATE400 starting current
- ≥5 ASource: ASD V3.2, PDF p.10, Table 2 starting-current row; ATE V2.9, PDF pp.5-6, ATE400 table
- Operating environment
- -10 to +55 °C; relative humidity ≤95%Source: ASD V3.2, PDF p.10, Table 2 Environmental requirement
CATALOGUE IMAGES
Additional views from the catalogue



CATALOGUE APPLICATION
Listed installation context
SOURCE DOCUMENTS
Original product manuals
ASD Switch Cabinet Integrated Measuring and Control Device — Installation and Operation Instruction
Chinese / English · V3.2 · Relevant PDF pages 6, 7, 8, 9, 10
Download original manual ↓PRODUCT QUESTIONS
Questions about this model
What does P12-C-400 identify?
The naming rule identifies P12 as 12 wireless temperature points, C as communication and 400 as ATE400 wireless temperature sensors.
What does TH-WH2 identify?
T selects opening/closing, remote/local and charging switches; H selects charging indication; WH2 selects two temperature/humidity control circuits.
Are these features shared by every ASD model?
No. These fields describe the catalog's ASD300-TH-WH2-P12-C-400 configuration. The manual assigns different functions to other ASD base models and ordering codes.
PROJECT SUPPORT
Evaluating ASD300-TH-WH2-P12-C-400?
Send the application, voltage, required functions, quantity and target delivery date.
Send project requirements →