CATALOGUE PRODUCT
ARTM-8L
Temperature Patrol Tester
Eight-channel wired temperature measurement and control instrument for low-voltage electrical contacts, transformer windings and motor windings.
← All products
ARTM-8L product photograph extracted from the supplied catalogue.PRODUCT IDENTITY
Catalogue record
- Source catalogue
- SST固态变压器配套产品明细.xls
- Original product name
- 有线测温装置
- Catalogue model
- ARTM-8L
- Source location
- Sheet1, row 20
- Catalogue installation location
- 输出柜
- Image source
- Sheet1!E20 · xl/media/image28.jpeg
- Maximum supported sensor ranges do not establish the range of an unspecified sensor assembly.
- The optional temperature/humidity input is not described as a standard included component.
PRODUCT OVERVIEW
Product information
The ARTM-8L accepts the specified NTC sensors, three-wire PT100/PT1000, K/T/J/E/N thermocouples and 0-5 V inputs. Its sensor-dependent measurement ranges, five normally-open alarm outputs, three analogue retransmission outputs and RS485 communication are listed in the manual's technical table.
Listed model
TECHNICAL DETAILS
Specifications and their sources
- Measurement channels
- 8Source: ARTM-8L T1.3, PDF p.7, section 1.2 Technical Features
- Input signals
- Specified NTC types; three-wire PT100/PT1000; K/T/J/E/N thermocouples; 0-5 VSource: ARTM-8L T1.3, PDF p.7, Input signal rows
- NTC measurement range / accuracy
- -40 to +140 °C /±1 °CSource: ARTM-8L T1.3, PDF p.8, Measurement Range and Accuracy class
- PT100/PT1000 measurement range
- Maximum supported -200 to +850 °C; actual range depends on the sensorSource: ARTM-8L T1.3, PDF p.8, Measurement Range
- PT100/PT1000 accuracy
- -200 to +200 °C: ±1 °C; above +200 to +850 °C: ±1%Source: ARTM-8L T1.3, PDF p.8, Accuracy class (standard signal)
- Thermocouple range / accuracy
- Maximum supported -200 to +1372 °C, actual range depends on thermocouple type; 1%Source: ARTM-8L T1.3, PDF p.8, Measurement Range and Accuracy class
- Auxiliary supply / consumption
- AC 85-265 V /DC 100-300 V; ≤2 WSource: ARTM-8L T1.3, PDF p.8, Auxiliary power
- Alarm outputs
- 5 groups normally open; AC 250 V /5 A or DC 30 V /5 ASource: ARTM-8L T1.3, PDF p.8, Alarm Output
- Analogue retransmission
- 3 channels, 4-20 mASource: ARTM-8L T1.3, PDF p.9, Transmit output
- Communication
- RS485, Modbus RTU; 2400 /4800 /9600 /19200 bpsSource: ARTM-8L T1.3, PDF p.9, Communication
- Operating environment / mounting
- -20 to +55 °C, humidity ≤95%; panel or DIN35 rail mountingSource: ARTM-8L T1.3, PDF p.9, Environment and section 1.3
CATALOGUE IMAGES
Additional views from the catalogue



CATALOGUE APPLICATION
Listed installation context
SOURCE DOCUMENTS
Original product manuals
ARTM-8L Temperature Patrol Tester — Operation Manual
Chinese / English / Russian · T1.3 · Relevant PDF pages 6, 7, 8, 9
Download original manual ↓PRODUCT QUESTIONS
Questions about this model
Is the same temperature range available with every sensor?
No. The table gives different ranges and accuracies for NTC, PT100/PT1000 and thermocouple inputs. The actual PT100/PT1000 and thermocouple ranges depend on the selected sensor.
How many alarm and retransmission outputs are listed?
The manual lists five normally-open alarm-output groups and three 4-20 mA retransmission channels.
Is the additional temperature/humidity input standard?
The manual identifies one temperature/humidity input as optional.
PROJECT SUPPORT
Evaluating ARTM-8L?
Send the application, voltage, required functions, quantity and target delivery date.