QUICK ANSWER

The practical starting point

Start with the measurement point and its operating conditions. ATE400 sends temperature wirelessly and obtains its power from the conductor current; ARTM-8L receives wired sensor signals. Selecting between them means checking a complete sensor-to-monitoring path, including power, installation, compatible interfaces and the required alarm response.

  • Check low-load conditions before selecting a CT-powered ATE400 sensor.
  • Treat the ARTM-8L input capability and the actual probe rating as separate requirements.
  • Specify receiver pairing, channel identification and alarm delivery as part of the purchase.
01

Compare measurement paths, not isolated instruments

A useful temperature-monitoring specification identifies the physical point, the sensor at that point, the device collecting its reading and the place where an operator sees an alarm. ATE400 and ARTM-8L occupy different positions in this chain. ATE400 is a sensor; ARTM-8L is an instrument that needs an appropriate wired input. Comparing their prices or channel counts alone would leave part of the system unspecified.

For a wireless proposal, document the sensor population, selected receiver, receiver power and onward communication. For a wired proposal, document the probe type, lead arrangement, instrument input and outputs. The comparison below is a project-planning framework; it does not establish that either arrangement is suitable for every cabinet or measurement point.

What the two measurement paths require
Design questionATE400 wireless pathARTM-8L wired path
Where does measurement start?ATE400 fixed at the selected electrical jointA separately selected probe or supported input signal
What supplies the sensing path?CT-induced power at the sensor; separate receiver supplyInstrument auxiliary supply and the selected sensor arrangement
What connects the point to the instrument?A matching radio-frequency and receiver configurationWiring appropriate to the selected input type
What completes the project?Verified reception, point mapping and onward alarmsVerified input configuration, point mapping and outputs
02

Use the starting-current condition in the decision

ATE400's CT-induced power removes the battery from this model's specification, but it creates a load-related selection condition. Review the expected conductor current during the operating states in which temperature visibility is required. A sensor chosen only against the feeder's rated current may not address the project's low-load or standby expectations.

The documented starting current is therefore a screening question, not a detail to leave until commissioning. If continuous readings at very low current are essential, obtain confirmation of the proposed arrangement before ordering. Do not promise a reporting interval for operating conditions outside the documented power condition.

ATE400Power source
CT-induced power; starting current ≥5 AATE V2.9, PDF pp.5-6, section 1.3 ATE400 table ↗
ATE400Sampling / transmission
15 s /15 sATE V2.9, PDF p.5, section 1.3 ATE400 table ↗
03

Select the probe before accepting the wired range

ARTM-8L supports several input families. Its maximum supported measurement range is an instrument capability, while the installed probe has its own sensing element, insulation, lead and mounting limits. The usable project range must fit the selected assembly and the instrument's applicable input specification.

The catalog includes a separate PT100 item but leaves its model field blank. That entry does not establish a probe-specific temperature range, accuracy class or insulation rating. Request the actual probe specification and confirm its lead arrangement before treating it as a complete ARTM-8L measurement channel.

ARTM-8L input selection: instrument capability and probe requirements
Model / parameterDocumented value & sourceWhat it means for selection
ARTM-8LInput signalsSpecified NTC types; three-wire PT100/PT1000; K/T/J/E/N thermocouples; 0-5 VARTM-8L T1.3, PDF p.7, Input signal rows ↗Identify the actual sensor type and lead arrangement before assigning the instrument input.
ARTM-8LPT100/PT1000 measurement rangeMaximum supported -200 to +850 °C; actual range depends on the sensorARTM-8L T1.3, PDF p.8, Measurement Range ↗Obtain the selected probe's own specification. The instrument's maximum supported range is not a rating for the catalog's unspecified PT100 assembly.
ARTM-8LMeasurement channels8ARTM-8L T1.3, PDF p.7, section 1.2 Technical Features ↗Allocate each required point to a named channel and keep that mapping in the handover record.

Values retain the original manual conditions. On a narrow screen, scroll the table sideways.

04

Resolve receiver pairing and physical routing

ATC600-C appears in the same catalog as ATE400. Its stated point capacity is useful for planning, but it does not establish radio coverage for a particular installed cabinet arrangement. Keep the sensor frequency, receiver configuration and intended locations together in the equipment schedule. The ATE400 distances below are open-area figures, not guaranteed cabinet-to-cabinet distances.

The receiver manual also separates compatible sensor groups. Its sharing note allows ATE210S with the listed ATE400/100/200 group only without a repeater, and excludes mixing that combination with other groups. A request for mixed sensors or repeaters therefore needs a configuration review, even when the total point count is below the receiver capacity.

ATE400Open-area communication distance
150 m at 470 MHz /868-923 MHz; 50 m at 433 MHzATE V2.9, PDF p.5, section 1.3 ATE400 table ↗
ATC600-CFunction / points
Receiver /240 temperature pointsATC600 V1.8, PDF pp.4-5, section 1.2 ATC600-C column ↗
05

Define what happens after a temperature is measured

A displayed value and a delivered alarm are different acceptance items. Decide where operators need the reading, which system receives the alarm and who maintains the point-to-equipment mapping. For a wired design, the ARTM-8L's alarm and retransmission outputs may be relevant to that interface review; their presence does not automatically complete the external control circuit.

For either architecture, prepare a point list with equipment identity, measurement location, channel or sensor identity, display name and destination. Specify alarm settings through the project's equipment and operating requirements. This guide does not supply one temperature threshold for every joint, winding or cabinet.

ARTM-8LAlarm outputs
5 groups normally open; AC 250 V /5 A or DC 30 V /5 AARTM-8L T1.3, PDF p.8, Alarm Output ↗
ARTM-8LAnalogue retransmission
3 channels, 4-20 mAARTM-8L T1.3, PDF p.9, Transmit output ↗
ATC600-CCommunication
RS485; Modbus RTU; 2400 /4800 /9600 /19200 bpsATC600 V1.8, PDF p.5, Communication, Baud rate and Protocol rows ↗
06

A worked selection discussion

Consider a hypothetical project with electrical joints requiring monitoring and a separate group of winding-temperature probes. The joint survey records available mounting positions, operating-current conditions and receiver locations. The winding survey records the installed probe type and lead arrangement. These are two measurement requirements, even if the owner wants their values on the same supervisory screen.

The next step is to qualify each path independently: verify the ATE400 power and reception conditions for the joints, then match the winding-probe documentation to an ARTM-8L input. The integration review can subsequently define common point names and alarm destinations. This approach produces a reviewable equipment schedule without assuming that one sensing method must serve every location.

Acceptance evidence to retain

Under the project's approved commissioning procedure, record each physical point's displayed identity, the corresponding supervisory value and the intended alarm indication. Retain the approved input configuration and receiver pairing alongside the test record.

RFQ CHECKLIST

Information to prepare

Use these items to turn a product discussion into a reviewable project specification.

  • Measurement locations and the operating states that require temperature visibility
  • ATE400 current conditions, fixing arrangement and selected frequency
  • Receiver model, sensor-group compatibility and any repeater requirement
  • Wired probe model, range, insulation details and lead arrangement
  • Instrument and receiver auxiliary supplies and environmental conditions
  • Point names, communication mapping and alarm destinations
  • Approved settings and evidence required for point-by-point acceptance
FAQ

Common questions

Does wireless mean that the whole monitoring system needs no power wiring?

No. ATE400 uses CT-induced power at the sensor. The receiver remains a separate device with its own supply requirements and interfaces.

Can I quote the ARTM-8L maximum range as the PT100 probe range?

No. The instrument's supported range is conditional on the sensor. The catalog's PT100 item has no model code or independent technical specification, so the selected probe needs separate confirmation.

Does receiver point capacity prove radio coverage?

No. Capacity and reception are separate checks. Match the frequency and sensor group, then verify the planned installation; open-area distance figures alone do not establish cabinet coverage.

SOURCE MANUALS

Check the original documentation

Product specifications above link to the relevant physical PDF pages. Project examples and checklists explain how to review a configuration; final settings and acceptance criteria belong in the approved project design.

EXTERNAL REFERENCES

Explore the wider technical context

These official references provide background. Product ratings come from the selected-model manuals above; a reference does not establish product certification. Standards pages offer public summaries; full texts may require purchase.